Reliable Load Testing, Precise Cooling
Load bank
Modular Load Bank be used to simulate the actual heating situation of the server room to detect the cooling effect of precision air conditioning. It has good load stability, high power accuracy, strong product availability, and suitable for Sigle Phase 230V power load testing. .It is suitable for computer room lines, load capacity, temperature rise, and precision air conditioning testing. Professional design, with the characteristics of safety, reliability, small size.
Testing System

UPS
POWER CABLE

LOAD BANK
RS485 CABLE

PC
PRINTER CABLE

PRINTER
System can do stable test, transient test, and realize functions, such as setting, fluctuation, instant load, and instant unload. The terms and formulas used in test strictly comply with relevant national standard.
Comprehensive Protection Function:
Multiple protection, like over temperature, smoke. When in danger, automatically terminate the test and give alarm to protect safety of personnel and
equipment.
Flexible Control Mode:
Based on different using habit, several control modes as following can be choose, local panel operation, remote box controlling, and intelligent software.
Technical Parameter 9-25kw
Modular Load Bank 9-25kw |
|
---|---|
Rated Voltage/Hz | 1Phase AC230V/50Hz |
Rated Power | Resistive: 25kw |
Load Resolution | Min 2kw Resistive Load
When voltage lower than 230V, the power will decrease according to Ohm’s Law. |
Power Factor | 1 |
Protection | IP21 |
Working Mode | Continuous |
Cooling | Force air cooling, front air intake, back air outlet 160CFM/Kw |
Colour | Green |
Dimension | 550mmx500x1250mm
(Length*Width*Height) |
Weight | Around 55-60kg |
Fan Power | 1Phase, 230VAC, Internal Lopped |
Workplace | Indoor |
Ambient Temperature | -10℃~+30℃ |
Relative Humidity | ≤95% |
Working power cable | 1 Set of 5pin industry plug with 5mts 5cx6sqmm flexible FR-LSH cable |
Transportation | 4Nos of Nylon wheels trolly Type |
Contactor and MCB | outgoing 16A and Fan 6A MCB |
Wiring | Port on load bank:
Wiring location: Top side of control box. |
Technical Parameter 100-2500kw
Modular Load Bank 500-2500kw |
|
---|---|
Rated Voltage/Hz | 400VAC, 3 phase 4wire 50Hz/60Hz |
Rated Power | Resistive: 100-2500kW |
Load Resolution | min step load: 1kW |
Power Factor | 1 |
Protection | IP21 |
Working Mode | Continuous |
Cooling | Force air cooling, horizontal air inlet & air outlet, with louver and
protection door |
Load Tolerance
(each step) |
±5% |
Dimension | About 1550mm*1250*1680mm For 500kw (L×W×H)
About 6550mm*2250*2680mm For 2500kw (L×W×H) |
Fan Power | 1Phase, 230VAC, Internal Lopped |
Load Tolerance
(overall) |
±3% |
Display Precision | 0.5 class |
Fan & Control Power | External 400VAC, 3 phase 4wire 50Hz |
Wire Connection | Load power supply input——Copper bar (star coupling)
Control power supply input——Connector-bar |
Transportation | 4Nos of Nylon wheels trolly Type And Hoisting, there are lifting lug on top |
Weight | About 650kgs for 500kw
About 12000kgs for 2500kw |
Wiring | Port on load bank:
Wiring location: Top side of control box. |