Reliable Load Testing, Precise Cooling

Load bank

Modular Load Bank be used to simulate the actual heating situation of the server room to detect the cooling effect of precision air conditioning. It has good load stability, high power accuracy, strong product availability, and suitable for Sigle Phase 230V power load testing. .It is suitable for computer room lines, load capacity, temperature rise, and precision air conditioning testing. Professional design, with the characteristics of safety, reliability, small size.

Testing System

UPS

UPS

POWER CABLE

Load Bank

LOAD BANK

RS485 CABLE

PC

PC

PRINTER CABLE

Printer

PRINTER

System can do stable test, transient test, and realize functions, such as setting, fluctuation, instant load, and instant unload. The terms and formulas used in test strictly comply with relevant national standard.

Comprehensive Protection Function:

Multiple protection, like over temperature, smoke. When in danger, automatically terminate the test and give alarm to protect safety of personnel and

equipment.

Flexible Control Mode:

Based on different using habit, several control modes as following can be choose, local panel operation, remote box controlling, and intelligent software.

Technical Parameter 9-25kw

Modular Load Bank 9-25kw

Rated  Voltage/Hz 1Phase AC230V/50Hz
Rated Power Resistive: 25kw
Load Resolution Min 2kw  Resistive Load

When voltage lower than 230V, the power will decrease according to

Ohm’s Law.

Power Factor 1
Protection IP21
Working Mode Continuous
Cooling Force air cooling, front air intake, back air outlet 160CFM/Kw
Colour Green
Dimension 550mmx500x1250mm

(Length*Width*Height)

Weight Around 55-60kg
Fan Power 1Phase, 230VAC, Internal Lopped
Workplace Indoor
Ambient Temperature -10℃~+30℃
Relative Humidity ≤95%
Working power cable 1 Set of 5pin industry plug with 5mts 5cx6sqmm flexible FR-LSH cable
Transportation 4Nos of Nylon wheels trolly Type
Contactor and MCB outgoing 16A and Fan 6A MCB
Wiring Port on load bank:

Wiring location: Top side of control box.

Technical Parameter 100-2500kw

Modular Load Bank 500-2500kw

Rated  Voltage/Hz 400VAC, 3 phase 4wire 50Hz/60Hz
Rated Power Resistive: 100-2500kW
Load Resolution min step load: 1kW
Power Factor 1
Protection IP21
Working Mode Continuous
Cooling Force air cooling, horizontal air inlet & air outlet, with louver and

protection door

Load Tolerance

(each step)

±5%
Dimension About 1550mm*1250*1680mm For 500kw (L×W×H)

About 6550mm*2250*2680mm For 2500kw (L×W×H)

Fan Power 1Phase, 230VAC, Internal Lopped
Load Tolerance

(overall)

±3%
Display Precision 0.5 class
Fan & Control Power External 400VAC, 3 phase 4wire 50Hz
Wire Connection Load power supply input——Copper bar (star coupling)

Control power supply input——Connector-bar

Transportation 4Nos of Nylon wheels trolly Type  And Hoisting, there are lifting lug on top
Weight About 650kgs for 500kw

About 12000kgs for 2500kw

Wiring Port on load bank:

Wiring location: Top side of control box.